Introduction:
- The DC MCCB 125A manufactured by CNTN Electric utilizes highly flame-retardant materials to effectively isolate electric arcs, while also providing protection against dust, moisture, and electric shock.
- CNTN Electric is capable of manufacturing not only 125A DC molded-case circuit breakers in accordance with customer requirements, but also models ranging from 100A to 630A.
- Our DC Molded Case Circuit Breakers (MCCBs) are suitable for three-phase four-wire circuits, and can also be used in three-phase three-wire and three-phase two-wire circuits.
- CNTN Electric manufactures not only AC 100A 4-pole molded case circuit breakers, but also DC molded case circuit breakers.
- CNTN Electric manufactures not only molded-case circuit breakers with white housings made of phenolic resin, but also those with gray and black housings made of plastic.
- The DC molded-case circuit breakers manufactured by CNTN Electric feature robust environmental adaptability, making them flexibly suitable for a wide range of application scenarios.
- Would you like to know the price of our 2P 80A MCB? Please contact us for more details now!
supsystic-tables id=58
| ZMM1 | MX | 1 | AC230V | |
| Model | Accessories | Adapter shell frame | Accessory voltage | |
| ZMM1 | OF: Auxiliary contact MX: Shunt release SD: Alarm module Z: Manual operation mechanism P: Electric operating mechanism TS2: Terminal shield 2P TS3: Terminal shield 3P | 1: 250/320 、 2: 400/630/800 | MX: AC110V、 AC230V、 AC400V、 DC24V、 DC110V、 DC220V 、 | P: AC400V、 AC230V、 DC220V |
Technical data
supsystic-tables id=57
| Model | ZMM1-630PV | ZMM1-800PV | |||||||
| Shell frame current Inm(A) | 630 | 800 | |||||||
| Number of poles of products | 2 | 3 | 2 | 3 | |||||
| DC working voltage(V) | 500 | 1000 | 1500 | 1500 | 500 | 1000 | 1500 | 1500 | |
| Rated insulation voltage Ui(V) | DC1500 | DC1500 | |||||||
| Rated impulse withstand voltage Uimp(KV) | Rated impulse withstand voltage Uimp(KV) | 12 | 12 | ||||||
| Rated current In(A) | 500,630 | 700,800 | |||||||
| Ultimate short - circuit breaking capacity Icu (kA) | S | 63 | 35 | 15 | 15/20 | 65 | 35 | 15 | 15/20 |
| N | 70 | 40 | 20 | 20/25 | 70 | 40 | 20 | 20/25 | |
| Running short - circuit breaking capacity Ics(kA) | Ics = 100%Icu | ||||||||
| Wiring method | Up in and down out, down in and up out, Down in and up out, up in and down out(3P) | ||||||||
| Isolation function | Yes | ||||||||
| Tripping type | Thermal - magnetic type | ||||||||
| Electrical life(time) | 1000 | 1000 | 700 | 500 | 1000 | 1000 | 700 | 500 | |
| Mechanical life(time) | 5000 | 5000 | |||||||
| Standard | IEC/EN60947 - 2 | ||||||||
| Attached accessories | Shunt,Alarm.Auxiliary,Manual operation,Electric operation | ||||||||
| Certifications | CE | ||||||||
| Overall dimension (mm) | Width(W) | 124 | 182 | 124 | 182 | ||||
| Height(H) | 250 | 250 | |||||||
| Depth(D) | 165 | 165 |
Codes for release devices and accessories
ZMM1-125 (L, M) front panel wiring (2-pole, 3-pole, 4-pole) (X-X, Y-Y are the centers of the 3-pole circuit breaker)
板前接线.jpg)
插入式板前接线.jpg)