| Model number | ZMGQ-40 |
| Power supply | 230VAC 50/60Hz |
| Max.Loading power | 1~40A Adjustable(default:40A) |
| 1~63A Adjustable(default:63A) |
| Over-voltage protection value range | 230V~300~OFF(default:270V) |
| Over-voltage recovery voltage range | 225V–295V(default:250V) |
| Over-voltage protection action time | 0.1s~30s(default value:0.5s) |
| Over-voltage r ecovery delay time | 1s~500s(default:30s) |
| Under-voltage protection value range | 140V–210V –OFF(default:170V) |
| Under-voltage recovery voltage range | 145V–215V (default:190V) |
| Under-voltage protection action time | 0.1s~30s(default:0.5s) |
| Under-voltage r ecovery delay time | 1s~500s(default:30s) |
| Over-current adjustment range | 1-40A (default:20A) 1-63A (default:40A) |
| Over-current action range | 0.1~30 second (default:0.5s) |
| Over-current r ecovery delay time | 1s~500s(default:30s) |
| Power-on delay time | 1s~500s(default:10s) |
| Power consumption | <2W |
| Electric machinery life | 100,000 times |
| Installation | 35mm DIN rail |