- The ZMW1 universal circuit breaker is a new – type circuit breaker developed by our company’s R & D technology. The product features small size, high breaking capacity, multiple functions, etc.
- The ZMW1 is suitable for general power distribution systems, new energy power generation and distribution systems, multi – power – source power distribution networks, inverters, and scenarios for grid – connection operation and protection of rotating motor – type power sources in distributed power sources.
- The ZMW1 complies with the GB14048.2 – Category B of the circuit breaker standards.
- AC – 3 category of use:
- The rated working voltage of the circuit breaker is 50Hz, AC400V/690V;
- The rated current of the circuit breaker is 200A ~ 1600A; The circuit breaker has three – pole and four – pole types;
- It has draw – out type and fixed type;
- It can be connected by reverse incoming line;
- It has an isolation function, with the symbol “__/| – × – ”.
- The circuit breaker complies with the following standards:
- IEC60947 – 1 and GB14048.1 – 2012 General Rules for Low – voltage Switchgear and Controlgear;
- IEC60947 – 2 and GB14048.2 – 2008 Circuit – breakers for Low – voltage Switchgear and Controlgear;
- IEC60947 – 4 – 1 and GB14048.4 Electromechanical Contactors and Motor Starters (including motor protectors) for Low – voltage Switchgear and Controlgear;
Main technical indicators
- WordPress Table
Type ZMW1-1600 Frame Size Rated Current lnm (A) 1600 Rated Current ln(A) 200,250,320,400,500,630,800,1000,1250,1600 Rated working voltage (V) AC50Hz/60Hz 400,600 Rated Insulation Voltage (V) 1000 Rated impulse withstand voltage (kV) 12 Power frequency withstand voltage (V)min 2500 Pole Number (P) 3,4 N-pole rated current (A) 100%ln Usage category GB14048.2 B GB14048.4(ln≤ 1000A) AC-3 Rated ultimate short-circuit breaking capacity AC400V 55 AC690V 42 Rated service short-circuit breaking capacity AC400V 50 AC690V 35 Rated short-circuit making capacity AC400V 143 AC690V 105 Rated short-time withstand voltage AC400V 50 AC690V 35 Total breaking time (without additional delay) (ms) 25 Closing time Maximum 70 Electrical life (times) AC400V ln=200A~1000A 1500 ln=1250A~1600A 1200 AC690V ln=200A~1000A 1000 ln=1250A~1600A 700 Mechanical life (times) Maintenance-free 3000 Maintenance-free 10000 Overall dimensions (width×depth×height) (mm) Fixed type 3P 260×310×240 Drawer type 3P 275×345×330 4P 330×310×240 4P 345×345×330 - WordPress Table
Item Number Standard inverse time Fast inverse time Extra-fast inverse time (for general purposes) Extra-fast inverse time (for motor protection) High-Voltage Fuse Compatible I²T 1 0.36(0.005) 1.00(1) 3.32(10) 2.94(10) 0.66(10) 8.43(15) 2 0.58(0.008) 1.60(1.6) 5.32(16) 4.72(16) 1.06(16) 16.87(30) 3 0.86(0.012) 2.40(2.4) 8.00(24) 7.06(24) 1.60(24) 33.75(60) 4 1.42(0.02) 4.00(4) 13.32(40) 11.78(40) 2.66(40) 67.50(120) 5 2.14(0.。03) 6.00(6) 20.00(60) 17.68(60) 4.00(60) 135(240) 6 2.86(0.04) 8.00(8) 26.66(80) 23.58(80) 5.32(80) 202.5(360) 7 3.58(0.05) 10.00(10) 33.30(100) 29.46(100) 6.66(100) 270(480) 8 5.36(0.075) 13.50(13.5) 45.00(135) 39.78(135) 9.00(135) —— 9 6.44(0.09) 18.00(18) 60.00(180) 53.04(180) 12.00(180) —— 10 10.02(0.14) 28.00(28) 93.32(280) 82.52(280) 18.66(280) —— 11 14.32(0.2) 40.00(40) 133(400) 117(400) 26.66(400) —— 12 21.48(0.3) 60.00(60) 200(600) 176(600) 40.00(600) —— 13 28.64(0.4) 80.00(80) 266(800) 235(800) 53.32(800) —— 14 35.80(0.5) 100(100) 333(1000) 294(1000) 66.66(1000) —— 15 42.98(0.6) 120(120) 400(1200) 353(1200) 80.00(1200) —— 16 50.14(0.7) 140(140) 433(1300) 383(1300) 86.66(1300) —— - Operation conditions
- WordPress Table
Item Description Ambient temperature -5℃~+40℃;the average value within 24h shall not exceed +35℃; L type and M type controller can be used under -40℃~+70℃ Altitude ≤ 2000m Pollution grade 3 Safety category Main circuit and undervoltage tripping coil is IV, other auxiliary and control circuit is III Installtion position Vertical installed, inclination between the mounting plane and the vertical plane should not exceed ±5° - Installation Dimensions of ZMW1 – 1600 Intelligent Universal Circuit Breaker (Drawout Type)
- Installation Dimensions of ZMW1 – 1600 Intelligent Universal Circuit Breaker (Fixed Type)
- WordPress Table
Rated current ln(A) 1600 2000 3200 4000 6300 Rated ultimate short circuit breaking capacity lcs(kA) 400/415V 65 80 100 120 135 660/690V 50 65 85 85 100 Rated service short circuit breaking capacity lcs(kA) 400/415V 55 65 80 100 135 660/690V 42 65 70 85 100 Rated short time withstand current lcw.1s(kA) 400/415V 50 65 80 100 135 660/690V 42 65 70 85 100 Rated short circuit making and breaking capacity lcm(kA) 400/415V 110 175 220 264 297 660/690V 77 143 154 187 220 Electric life 8000 8000 8000 6000 1500 Mechanical life (Maintenance) 30000 30000 20000 20000 5000 Mechanical life (Non-maintenance) 20000 15000 12500 10000 2500 Dimension(mm)W×H×L Drawout type 3P 285*345*351 375*451*432 435*486*439 453*486*439 930*486*439 4P 352*345*351 470*451*432 550*486*439 550*486*439 930*486*439 Fixed type 3P 254*251*320 362*362*395 426*378*395 426*378*395 930*486*439 4P 342*251*320 457*362*395 537*378*395 537*378*395 930*486*439
Universal Circuit Breaker ZMW1 Air Circuit Breaker (ACB)
Key features: