Our 3 Phase Din Rail Energy Meter DTSU2788 and DSSU2788 both adopt microelectronics technology and are used to measure the active electrical energy of three-phase AC with a rated frequency of 50/60HZ.
They measure the electricity consumption in both forward and reverse directions equally. There are two connection methods for this series of electronic three-phase watt-hour meters: direct connection type or connection via mutual inductor type.
This 3 Phase Din Rail Energy Meter all the technical requirements for din-rail three-phase electric energy meters specified in the national standard GB/T17215.321-2008 《Class 1 and Class 2 Static AC Active Watt-Hour Meters》
Technical Functions
- Measures three – phase active electrical energy, no need for calibration during long – term operation.
- Powered by three – phase power supply. If one wire (any one of the three wires of a three – phase three – wire electric energy meter) or two wires (any two of the four wires of a three – phase four – wire electric energy meter) is disconnected, the measurement accuracy is not affected.
- Wide operating temperature range.
- Has phase – failure indication function or voltage indication function
- Display methods: counter, liquid crystal.
- Has remote power – off function.
- Output interface: RS485.
Technical Index | Data |
Rated voltage AC | DTSU2788 three phase four wire 3x120/208V,3x220/380V,3x230/400V,3x240/415V |
Working voltage range | 0.8~1.2Un |
Rated current | 5ACT,1.5(6)A,5(60)A,10(100A,or other as required |
Frequency | 50Hz or 60Hz |
Connection mode | CT type or Direct type |
Display | mechanical step register or LCD |
Accuracy class | 1 |
Power consumption | <0.5W/5VA/each phase |
Start current | 0.004lb |
AC voltage withstand | 4000V/25mA for 60 seconds |
Impulse voltage | 6kV 1.2 μs waveform |
IP grade | IP20 |
Constant | 400~6400 imp/kWh |
Pulse output | Passive pulse,pulse width is 80±5ms |
Executive standard | DIN 43880,IEC62053-21,IEC62052-11 |
Work temperature | -30℃~70℃ |
Outline dimension L×M×H | 125x88x73mm |
Operating temperature | -25℃~55℃ |
Storage temperature | -40℃~80℃ |
Reference temperature | 23℃±2℃ |
Relative humidity | 0 to 95%,non-condensing |
Altitude | Up to 2500m |
Warm up time | 10s |
Mechanical Environment | M1 |
Electromagnetic Environment | E2 |
Degree of pollution | 2 |